Call us at 816-524-8100 for pricing on systems with more than 10 sensors
This is a complete Carbon Monoxide and Nitrogen Dioxide (NO2) gas monitoring system with one Macurco DVP-1200 Controller and CX-6 CO/NO2 gas monitors.
Here are some additional details:
DVP-1200 with Digital w/ BACnet IP Controller Assembly
Click here for Specifications and details
Here is a quick summary of the Controller
The DVP-1200 controller in conjunction with Macurco gas detectors provides automatic control to help maintain an acceptable environment in parking garages or other applications. This control panel offers an expandable system with up to 192 addressable detectors in the field. The DVP-1200 comes standard with four relays, as well as expandable onboard relay options (+2, +4). Other outputs on the DVP-1200 include three analog outputs, four 24VDC drivers, and BACnet IP. The DVP-1200 can be connected to up to two remote relay boxes with each remote relay box containing two relays. With the expandability of this panel, the DVP-1200 will fit into any gas detection application.- ETL Listed, LADBS Approved
Key Features
-
90-250 VAC input
-
Three RS-485 channels can connect up to 192 detectors (64 per channel)
-
Up to 12 relays
• Standard with four onboard relays
• Up to four optional onboard expansion relays (+2 or +4)
• Can be connected to two remote relay boxes (two relays in each box) -
(3) 4-20mA outputs for VFD control
-
(4) 24VDC outputs for alarm, trouble, remote notification
-
BACnet IP (ethernet connection)
-
Lockable NEMA4x type enclosure
-
A total of eight zones can be defined
-
Event logging
CX-6 Gas Monitor with CO and NO2 Sensors
Click here for Specifications and details
Here is a quick summary of the gas monitor
CO/NO2 - Low Voltage
The CX-6 low voltage dual monitor detects Carbon Monoxide and Nitrogen Dioxide in commercial facilities such as parking garages, loading docks, etc. It can be used as a stand-alone detector, controller and as an analog transducer for use with Macurco control panels and other systems – ETL Listed
Key Features
- Digital Display for CO & NO2
- Internal Buzzer
- Replaceable Sensors
- End of Life Notification
- 12-24VAC or 12-32VDC input
- 5A SPDT Fan control relay, 0.5A N.O. or N.C. Alarm Relay
- Selectable Fan and Alarm Relay Actuation Settings
- 4-20mA current loop